APC ACPCW40-150 Air Conditioner User Manual


 
43InRoom Precision AC Tech Data Manual
60Hz InRoom Electrical Specifications
Air Cooled (DX) and Fluid Cooled (Glycol) Electrical Data
With Reheat and
Humidification
Without Reheat and
Humidification
Compressor
Data
Model
Size
Airflow
Pattern
Cooling System
Voltage
(3ph/60Hz)
MCA MOP
Power
(kW)
MCA MOP
Power
(kW)
LRA RLA
211
Up/
Down
PAXXX
PGXXX
PACWXXX
PGCWXXX
208-230 67.3 70 20.6 33.3 50 10.6 137 19.3
460-480 34.5 35 21.0 15.6 20 9.9 62 9.1
575-600 30.2 35 29.3 15.2 20 11.3 62 9.1
PGEXXX
208-230 84.3 90 25.7 33.3 50 10.6 137 19.3
460-480 43.8 50 26.6 15.6 20 9.9 62 9.1
575-600 37.7 40 39.3 15.2 20 11.3 62 9.1
311
Up/
Down
PAXXX
PGXXX
PACWXXX
PGCWXXX
208-230 100.3 125 30.4 49.3 80 15.3 195 32.1
460-480 53.0 60 32.0 24.7 40 15.3 95 16.4
575-600 42.2 45 32.3 19.9 30 14.3 95 16.4
PGEXXX
208-230 109.5 125 30.4 49.3 80 15.3 195 32.1
460-480 57.2 60 32.0 24.7 40 15.3 95 16.4
575-600 45.8 50 35.7 23.3 35 17.7 95 16.4
452
Up/
Down
PAXXX
PGXXX
PACWXXX
PGCWXXX
208-230 116.0 125 37.3 65.0 80 22.2 156 20.7
460-480 59.2 60 37.8 30.9 40 21.0 75 10.0
575-600 42.5 45 36 29.3 35 24.7 75 10.0
PGEXXX
208-230 141.6 150 44.9 65.0 80 22.2 156 20.7
460-480 73.4 80 46.2 30.9 40 21.0 75 10.0
575-600 53.7 60 43.5 29.3 35 24.7 75 10.0
612
Up/
Down
PAXXX
PGXXX
PACWXXX
PGCWXXX
208-230 167.3 175 53.3 90.6 100 30.6 195 32.1
460-480 87.8 90 55.7 45.3 60 30.5 95 16.4
575-600 57.1 60 44.7 35.3 45 27.1 95 16.4
PGEXXX
208-230 176.5 200 56.7 99.8 125 34.0 195 32.1
460-480 92.0 100 58.8 49.5 60 33.6 95 16.4
575-600 60.5 70 48.1 38.7 50 30.5 95 16.4
862
Up/
Down
PAXXX
PGXXX
PACWXXX
PGCWXXX
208-230 210.2 225 67.8 133.6 175 45.1 245 47.1
460-480 104.8 125 67.3 62.3 80 42.1 125 22.1
575-600 65.4 70 51.9 47.5 60 38.1 125 22.1
Note: Above data is based on maximum operating conditions
Installation must comply with all local and/or national electrical codes.
MCA - Minimum Circuit Ampacity
MOP - Maximum Overcurrent Protection
LRA - Compressor Locked Rotor Amps
RLA - Compressor Rated Load Amps