APC ACPCW40-150 Air Conditioner User Manual


 
InRoom Precision AC Tech Data Manual46
Chilled Water Continued PCW400
Cabinet Size 1
PCW660
Cabinet Size 2
PCW900
Cabinet Size 3
PCW1100
Cabinet Size 4
PCW1500
Cabinet Size 5
Fan Information
Number of Fans12223
Air Flow - M³/hr (CFM) 8495 (5,000) 12997 (7,650) 18995 (11,180) 22002 (12,950) 29495 (17,360)
External Static Pressure - Pa (in WC) 50 (0.2) 50 (0.2) 50 (0.2) 50 (0.2) 50 (0.2)
Sound Power Level - dBA 72.1 75.2 79.1 85.7 86.7
Total Fan Power Consumption - kW (hp) 1.7 (2.3) 2.6 (3.5) 5.3 (7.1) 5.4 (7.2) 8.8 (11.8)
Connection Sizes
Upflow Chilled Water In/Out - mm (in) 35 (1 3/8) 42 (1 5/8) 54 (2 1/8) 70 (2 3/4) 70 (2 3/4)
Downflow Chilled Water In/Out - mm (in) 35 (1 3/8) 42 (1 5/8 54 (2 1/8) 54 (2 1/8) 54 (2 1/8)
Humidifier Supply Line - mm (in) 6 (1/4) 6 (1/4) 6 (1/4) 6 (1/4) 6 (1/4)
Condensate Drain Line - mm OD (in ID) 21 (3/4) 21 (3/4) 21 (3/4) 21 (3/4) 21 (3/4)
Humidification – Solid State Electrode, Canister
Flush Cycle Automatic Automatic Automatic Automatic Automatic
kg/hr (lb/hr) 8.0 (17.6) 8.0 (17.6) 15.0 (33.1) 15.0 (33.1 15.0 (33.1)
Electric Reheat – Equally Loaded Three (3) phase
Capacity - kW (BTU/hr) - Includes Motor Heat
400 V 12 (40982.4) 18 (61473.6) 18 (61473.6) 27 (92210.4) 27 (92210.4)
Number of Stages12233
Downflow Filters - mm Quantities
836 x 546 x 92 G4 N/A N/A 3 3 3
836 x 393 x 92 G4 N/A 1 N/A 1 2
836 x 446 x 92 G4 2 2 N/A N/A N/A
Upflow Filters - mm Quantities
795 x 508 x 92 G4 N/A N/A 1 2 2
795 x 341 x 92 G4 1 1 N/A 1 1
795 x 333 x 92 G4 N/A 1 N/A N/A 1
795 x 365 x 92 G4 N/A N/A 1 1 1
795 x 516 x 92 G4 N/A N/A 1 N/A N/A
795 x 502 x 92 G4 1 1 N/A N/A N/A
Physical Data
Weight - kg (lb) 307 (677) 362 (798) 547 (1206) 568 (1252) 755 (1664)
Height - mm (in) 1980 (77.95) 1980 (77.95) 1980 (77.95) 1980 (77.95) 1980 (77.95)
Width - mm (in) 1000 (39.37) 1400 (55.11) 1750 (68.90) 2150 (84.65) 2550 (100.39)
Depth - mm (in) 890 (35) 890 (35) 890 (35) 890 (35) 890 (35)