APC ACPCW40-150 Air Conditioner User Manual


 
InRoom Precision AC Tech Data Manual44
Chilled Water (CW) Electrical Data
With Reheat and
Humidification
Without Reheat and
Humidification
Model
Size
Airflow
Pattern
Cooling System
Voltage
(3ph/60Hz)
MCA MOP
Power
(kW)
MCA MOP
Power
(kW)
400 Down PCWXXX
208-230 59.0 60 18.8 9.9 15 3.1
460-480 32.7 35 20.8 4.4 15 2.8
575-600 28.7 30 22.9 6.2 15 4.9
400 Up PCWXXX
208-230 60.6 70 19.3 11.5 20 3.7
460-480 33.5 35 21.4 5.3 15 3.3
575-600 28.7 30 22.9 6.2 15 4.9
660 Up/Down PCWXXX
208-230 91.6 100 29.2 19.8 25 6.3
460-480 46.5 50 29.6 8.9 15 5.7
575-600 39.7 40 31.7 9.7 15 7.7
900 Up/Down PCWXXX
208-230 109.4 125 34.9 23.0 25 7.3
460-480 56.4 60 35.9 10.5 15 6.7
575-600 47 50 37.6 10.4 15 8.3
1100 Up/Down PCWXXX
208-230 135.0 150 43.0 23.0 25 7.3
460-480 70.6 80 45.0 10.5 15 6.7
575-600 47 50 37.6 10.4 15 8.3
1500 Up/Down PCWXXX
208-230 146.5 150 46.7 34.5 35 11.0
460-480 75.9 80 48.4 15.8 20 10.0
575-600 62.5 70 50 14.7 20 11.7
Note: Above data is based on maximum operating conditions
Installation must comply with all local and/or national electrical codes.
MCA - Minimum Circuit Ampacity
MOP - Maximum Overcurrent Protection
LRA - Compressor Locked Rotor Amps
RLA - Compressor Rated Load Amps