APC 40 130KVA Fan User Manual


 
MGE Galaxy 5000
A — 4 86-174010-00 B00
General characteristics of Galaxy 5000 UPSs
INFORMATION The operating temperature range is 32°F to 104°F (0°C to +40°C); for overload
conditions is 32°F to 86°F (0°C to +30°C). Optimum operating range is within 68°F
to 77°F (20°C to +25°C). Battery backup time is adversely affected by high and low
temperatures. It is significantly reduced at temperatures under 50°F (10°C). Above
77°F (25°C), battery service life is cut in half every 18°F (10°C). Above 104°F (40°C),
battery manufacturers no longer guarantee operation due to the risk of thermal
runaway.
UPS power in KVA 40 50 60 80 100 130
Normal AC input
Number of conductors 3 phases + ground
Reference voltage at Pn 432 V to 528 V
Reference frequency 45 Hz to 65 Hz
THDI Typically 3% at Pn
Power factor >0.99
Bypass AC input
Number of conductors 3 phases + ground
Reference voltage at Pn 432 V to 528 V
Reference frequency 45 Hz to 65 Hz
Load output
Number of conductors 3 phases
Set phase-to-phase voltages 480 V
Voltage variation ± 1%
Adjustable frequencies and
tolerance (on battery power)
60 Hz ± 0.1 Hz
Voltage variation for 0 to
100% load step change
± 1%
Permissible overloads 150% for 1 minute, 125% for 10 minutes
THDU Ph-to-Ph and Ph-to-N
for nonlinear load
< 2% Ph-to-Ph
Battery
Standard battery technology Sealed lead-acid battery (gas-recombination)
Inverter
Active power (kW) 36 45 54 72 90 117
Heat losses in kW Heat
Heat losses in BTUs
2.71
9250
3.39
11560
4.06
13870
5.42
18500
5.74
19610
7.47
25490
Storage temperature range -13°F to 103°F (-25°C to +45°C)
Relative humidity 20% to 95%
Maximum operating altitude
without derating
3281 ft (< 1000 m)
Operating temperature range
at Pn
32°F to 104°F (0°C to 40°C)
Appendices