APC 40 130KVA Fan User Manual


 
2.8.1 Characteristics of the Contacts on the Relay Communications Card
Figure 2-13: Characteristics of the Contacts on the Relay Communications Card
Communications Card Connection Example
If a SELV (safety extra low voltage) source is used, it must always be possible to isolate the communications card from
the upstream source to ensure the safety of personnel working on the installation.
Disconnecting device that can be locked
AC
communication
card
UPS OFF
UPS ON
Low battery warning
Load on battery power
Load on automatic bypass
Load on UPS
Battery fault
General alarm
Characteristics of the output contacts:
Permissible voltage: 250V AC, 30V DC.
Permissible current: 2 A.
Cable: 4 x 0.93 mm2, Ø 6.6 ± 0.3 mm.
Characteristics of the input contacts:
Switched voltage: 5 V DC
Consumption: 10 mA.
Cable: 4 x 0.34 mm2, Ø 5 ± 0.5 mm.
MGE Galaxy 5000
Setup and Installation2 — 10 86-174010-00 B00