Installation and User Manual
1 — 386-174010-00 B00
1.2 Inside the UPS Cabinet, Access to Connections
Figure 1-3: Inside MGE Galaxy 5000 UPS Cabinet
(1) Connectors for auxiliary interconnections of
parallel UPS units (INTN PCA), optional
(2) User-machine interface display
(3) Slot for relay communications card
(4) Open slots for optional communication cards
(5) Open cabinet door
(6) Screw-type terminal block for connections of
contacts and coils for two external battery
circuit breakers XMB07, XMB08
(7) Screw-type terminal block for connection of
remote emergency power off (REPO) XMB06
(
(
8) Q1: input switch for normal AC input
(9) Q4S: input switch for bypass AC input
(10) Q3BP: bypass switch
(11) Q5N: UPS output switch
(12) Protection cover for power connections
(13) Screw-type terminal block for connection of
contacts for parallel circuit breakers TB6,
optional
Introduction