APC 40 130KVA Fan User Manual


 
3.8 UPS Personalization
Access to the Personalization Functions
CAUTION Personalization must be carried out with switches Q1 (8) and Q5N (11) open (OFF)
and switch Q4S (9) closed (ON).
Figure 3-8: UPS Personalization
Personalization Settings
Operating Mode
Frequency
Automatic Bypass
Transfer to bypass AC source Enabled
Disabled – disabled when
limiting
Transfer to bypass with bypass AC source out of
tolerances
Enabled Disabled
UPS output frequency 60 Hz 60Hz
Tolerance for bypass AC source 8 % 0.5 - 1 - 2 - 4 %
Synchronization speed with bypass AC source 2 Hz / s 1 Hz / s
Function Factory setting Options
UPS operating mode NORMAL
UPS automatic start Disabled Enabled
Authorized number of starts 4 1 to 255
Delay before reset of number of executed
automatic starts
4 seconds 1 to 60 seconds
The password
To change the password, see the Settings menu.
1 - Press the menu key (36).
2 - Select "Settings", then "Personalization" using the
function keys (35) or .
3 - Confirm by pressing the function key (35) .
4 - Enter the password by successively selecting each icon
using the corresponding function key.
5 - Confirm by pressing the function key (35) .
6 - To save the personalization settings, confirm by
pressing the function key (35) .
is factory set.
MGE Galaxy 5000
Operation3 — 6 86-174010-00 B00