3.8 UPS Personalization
Access to the Personalization Functions
CAUTION Personalization must be carried out with switches Q1 (8) and Q5N (11) open (OFF)
and switch Q4S (9) closed (ON).
Figure 3-8: UPS Personalization
Personalization Settings
Operating Mode
Frequency
Automatic Bypass
Transfer to bypass AC source Enabled
Disabled – disabled when
limiting
Transfer to bypass with bypass AC source out of
tolerances
Enabled Disabled
UPS output frequency 60 Hz 60Hz
Tolerance for bypass AC source 8 % 0.5 - 1 - 2 - 4 %
Synchronization speed with bypass AC source 2 Hz / s 1 Hz / s
Function Factory setting Options
UPS operating mode NORMAL
UPS automatic start Disabled Enabled
Authorized number of starts 4 1 to 255
Delay before reset of number of executed
automatic starts
4 seconds 1 to 60 seconds
The password
To change the password, see the Settings menu.
1 - Press the menu key (36).
2 - Select "Settings", then "Personalization" using the
function keys (35) or .
3 - Confirm by pressing the function key (35) .
4 - Enter the password by successively selecting each icon
using the corresponding function key.
5 - Confirm by pressing the function key (35) .
6 - To save the personalization settings, confirm by
pressing the function key (35) .
is factory set.
MGE Galaxy 5000
Operation3 — 6 86-174010-00 B00