APC 40 130KVA Fan User Manual


 
Installation and User Manual
Fitting the Protection Cover for the Auxiliary Interconnection Cables
The protection cover supplied with the parallel connected UPS units protects the user against direct contact with
voltages other than SELVs and ensures the auxiliary interconnection cables are maintained in position.
Figure 2-9: Fitting the Protection Cover for the Auxiliary Interconnection Cables
Note: Tie down the cables as indicated in the diagram in Section 2.9.
2.6 Connection of General Shutdown or Remote Emergency Power Off (REPO) Terminal Block
Figure 2-10: Connection of General Shutdown or Remote Emergency Power OFF (REPO) Terminal Block
CAUTION Pressing the general shutdown button causes UPS shutdown and opening of the
battery circuit breaker (with opening of the bypass static switch depending on
personalization settings). The Remote Emergency Power Off (REPO) notion is
applicable to installations where pressing the button also causes the upstream
Normal AC source and bypass AC source circuit-breakers to open. In parallel
configurations, there must be a single general shutdown button with a separate
contact for each UPS unit.
1 - Remove the wire jumper from terminal block (7).
2 - Connect the general shutdown NC contact to terminals 1 and 2 (SELV).
3 - Tie the cable down as illustrated in Section 2.9.
XMB08 XMB07 XMB06
Setup and Installation 2 — 786-174010-00 B00