APC 40 130KVA Fan User Manual


 
3.5 Operation of Mimic-Panel LEDs
The MGE Galaxy 5000 system is simple to operate and yet provides a wealth of continuous monitoring and
diagnostic features to ensure proper operation. Operators gain access to information in the MGE Galaxy 5000
system through the display and its integrated LED mimic panel.
Figure 3-5: Operation of Mimic-Panel LEDs
Single UPS Start Sequence on Normal AC Input
Single UPS Start Sequence on Bypass AC Input
Steps Action LED (39) LED (40) LED (41) LED (42) LED (43)
1 Q4S open Off Off Off Off Off
2 Close Q4S Off Off red Off green
3 Close Q5N Off Off red green green
4 Open Q3BP Off Off red green green
5 Close Q1 green Off red green green
6 Close Battery CB green Off Off green green
7 Press ON button (37) green green Off green Off
Steps Action LED (39) LED (40) LED (41) LED (42) LED (43)
1 Q1 open Off Off Off Off Off
2 Close Q1 green Off red Off red
3 Close Battery CB green Off Off Off red
4 Close Q4S green Off Off Off green
5 Close Q5N green Off Off green green
6 Open Q3BP green Off Off green green
7 Press ON button (37) green green Off green Off
37
MGE Galaxy 5000
Operation3 — 4 86-174010-00 B00