Product Description Optional Modules
20 Unimode 9600 PN 51336:C 11/06/01
1.6.3 300 Series Intelligent Addressable Devices
ADT’s 300 Series Intelligent Addressable Devices are fully compatible with the Unimode
9600 FACP. The devices must be configured for CLIP Mode operation if the control panel
is installed in an existing system with 300 Series devices. The address of 300 Series
devices cannot be set above 99. Compatible devices include:
• SD300 Photoelectric Detector
• SD300T Photoelectric Detector with Thermal Sensor
• CP300 Ionization Detector
• M300 Monitor Module
• M301 Miniature Monitor Module
• M302 2-wire Monitor Module
• C304 Control/Relay Module
• ADT-BG-10LX Manual Pull Station
1.6.4 Addressable Device Accessories
End-of-Line Resistor Assembly P/N R-47K
The 47 kΩ End-of-Line Resistor assembly (P/N: R-47K) is used to supervise the MMF-
300, MDF-300, MMF-301 and CMF-300 module circuits. The 3.9 kΩ End-of-Line
Resistor assembly is used to supervise the MMF-302 module circuit. The resistors are
included with each module.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4-
wire smoke detectors and notification appliances.
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate which is required for use in Canada. An
ELR, which is supplied with each module and fire alarm control panel, is mounted to the
ELR plate. Resistors mounted to the N-ELR plate can be used for the supervision of a
monitor and control module circuit.
1.7 Optional Modules
The Unimode 9600 main circuit board includes option module connectors for the
following modules:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter,
alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED.
A jumper on the module is used to select an option which allows the reverse polarity
circuit to open with a system trouble condition if no alarm condition exists. The module
plugs into connectors J10 and J11 which are located near the top center of the main circuit
board. When the 4XTMF module is installed, Jumper JP6, on the main circuit board, must
be cut to allow supervision of the module.
SLC-2 Expander Module
The SLC-2 Expander Module allows expansion of the Unimode 9600 from one SLC
circuit to two SLC circuits. The module plugs into connector J3 which is located in the
lower right corner of the main circuit board. The wiring for the second SLC connects to
terminals located on the expander module.