ADT Security Services 9600 Smoke Alarm User Manual


 
Product Description Components
18 Unimode 9600 PN 51336:C 11/06/01
Cabinet
The Unimode 9600 cabinet is red with a navy blue front overlay.
The backbox provides space for two batteries (up to 18 Amp
Hour). Ample knockouts are provided for system wiring. Also
included is a standard dress panel, which mounts to the inside of
the cabinet (required on the ULC version). The dress panel must
be installed to meet FM requirements.
Batteries
The Unimode 9600 cabinet provides space for two batteries (up to
18 Amp Hour). Batteries larger than 18 Amp Hour up to 25 Amp Hour require use of UL
listed battery cabinet. The ADT-CHG-120 can be used for charging 25 to 120 AH
batteries and the BB-55F can be used for housing the batteries. Batteries must be ordered
separately.
1.6.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC
Signaling Line Circuit (refer to the ADT SLC Wiring Manual for detailed information on
device installation, wiring and operation). This allows the control panel to continually
process the information to determine the status (alarm, trouble, maintenance or normal) of
each detector. Each detector responds to an SLC address that is set in the detector head
using built-in rotary decimal switches with the ability to select up to 159 addresses. Note
that a blinking LED on an intelligent detector indicates communication between the
detector and the control panel. Refer to the ADT Device Compatibility Document for a
list of approved detectors.
Smoke Detectors (Photoelectric)
The SD350 is an intelligent, addressable low profile photoelectric smoke detector which
provides smoke sensing technology. The SD350T includes a 135
o
fixed thermal sensor.
Smoke Detector (Ionization)
The CP350 is an intelligent, addressable low profile ionization smoke detector which
measures the level of combustion products in its chamber using the ‘ionization principle.’
Smoke Detector (Duct)
The D350P is an intelligent, addressable photoelectric duct smoke detector. The D350RP
includes an alarm relay.
Heat Detectors
The H350 is an intelligent heat detector with a thermistor sensing circuit for fast response,
designed to provide open area protection with 50 foot (15 m) spacing capability. The
H350R incorporates a thermal Rate-of-Rise circuit of 15
o
F (9.4
o
C).
Detector Bases
The B501BH is a standard sounder base and the B501BHT is a temporal tone sounder
base for intelligent, addressable smoke detectors.
The B224RB is a relay base with one Form-C relay for intelligent, addressable smoke
detectors. It may be used to control auxiliary functions.
The B224BI is an isolator base for intelligent, addressable smoke detectors. It functions
similar to the I300 isolator module which allows loops to operate under fault conditions
and automatically restore when the fault is removed.
uni-600.cdr