14 Unimode 9600 PN 51336:C 11/06/01
1.3 Specifications
AC Power - TB1
120 VAC, 60 Hz, 3.2 amps
Wire size: minimum 14 AWG (2.00 mm
2
) with 600 V insulation
Battery (Lead Acid Only) - TB2
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.00 amp
Maximum Battery Charger Capacity: 25 Amp Hour (Unimode 9600 cabinet holds
maximum of two 18 Amp Hour batteries. For greater than 25 Amp Hour up to 120 Amp
Hour batteries, use the ADT-CHG-120 Battery Charger and BB-55F Battery Box.
Note: Jumper JP3, on the FACP main circuit board, must be cut to disable the FACP
battery charger when using the ADT-CHG-120.
Communication Loop - (Standard ) TB8 and (Optional SLC Expander Module) J3
24 VDC nominal, 27.6 VDC maximum
Maximum length is 10,000 ft. (3,000 m) total twisted, shielded pair length
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited
Refer to SLC Loop manual for wiring information
Notification Appliance Circuits - TB4
Power-limited circuitry
Maximum voltage drop in wiring: 2.0 VDC
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
Maximum signaling current per circuit: 3.00 amps (see Figure 1.1 on page 15)
End-of-Line Resistor: 4.7 k, ½ watt (P/N 71252 UL listed) for NACs
Refer to ADT Device Compatibility Document for listed compatible devices
Two Programmable and One Fixed Output Relay - TB5
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays
Refer to Figure 2.5 on page 28 for information on power-limited wiring for relay circuits
Four-Wire Resettable Smoke Detector Power (24 VDC nominal) - TB3,
Terminals 1 (+) & 2 (-)
Maximum ripple voltage: 10 mV
RMS
Up to 3.0 amps is available for powering 4-wire smoke detectors (see Figure 1.1)
Power-limited circuit
Refer to ADT Device Compatibility Document for listed compatible devices
Nonresettable Power #1 (24 VDC Nominal) - TB3, Terminals 3 (+) & 4 (-)
Maximum ripple voltage: 10mV
RMS
Total DC current available from each output is up to 3.00 amps (see Figure 1.1)
Power-limited circuit
Nonresettable Power #2 (24 VDC Nominal) - TB3, Terminals 5 (+) & 6 (-)
Maximum ripple voltage: 10mV
RMS
Total DC current available from each output is up to 3.00 amps (see Figure 1.1)
Power-limited circuit