Pressing 3 while viewing Program Check screen will cause a screen similar to the
following to be displayed:
The Zone No Output feature allows the programmer to view the zones which have not
been programmed to at least one output device (not including general alarm Zone 00). The
example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been
programmed to an addressable detector with an address of 001 on loop 1 but have not been
programmed to any output devices. Use the up and down arrow keys to view all the zones
without output assignments.
3.7.4 Walktest
To perform a walktest, press 1 while viewing Maintenance Screen #2. The following
screen will be displayed:
The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest.
The display will read UNIT IN WALKTEST. To end the Walktest, press the Esc (Escape)
key.
Pressing 3 after the walktest has been completed, will allow the operator to view the
results of the walktest.
3.7.5 System
To program the time and date into the control panel, press 2 while viewing Maintenance
Screen #2. The following display will appear:
@@@ZONES@NO@OUTPUT
05@07@09@10@11@1D001
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
@@@@@WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW@RESULT
Walktest Screen
@@@@@SYSTEMS
1=TIME/DATE
System Screen