York 122 Heat Pump User Manual


 
12
Cooling capacities
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
W
W
kW
W
kW
W
kW
W
kW
45
4035
25 30
YLCC-122
kW
YLCC-102
YLCC-152
DB air temperature at condenser intake °C
Capacity
Leaving
water
temp.
°C
Model
Consump.
Capacity
Consump.
Capacity
Consump.
Capacity
Consump.
Capacity
Consump.
105 806 39.86 97 638 41.21 90 526 42.10 81 877 43.45 74 381 43.22
109 458 40.76 101 097 42.10 93 217 43.45 85 433 44.34 77 361 45.69
113 110 41.21 104 749 43.00 96 100 44.79 88 412 45.69 80 628 47.03
116 954 42.10 108 497 43.89 100 232 45.69 91 872 46.58 83 607 47.93
120 702 43.00 112 245 44.79 103 788 46.58 95 331 47.93 86 971 49.27
124 834 43.89 116 089 45.69 107 440 47.48 98 503 48.82 89 950 50.61
128 870 44.79 119 837 46.58 111 092 48.37 102 250 50.16 93 025 51.51
132 810 45.69 123 777 47.48 114 840 49.27 105 806 51.06 98 887 52.85
127 716 57.21 117 856 59.14 109 272 60.42 98 832 62.35 89 784 62.03
132 124 58.49 122 032 60.42 112 520 62.35 103 124 63.64 93 380 65.57
136 532 59.14 126 440 61.71 116 000 64.28 106 720 65.57 97 324 67.49
141 172 60.42 130 964 62.99 120 988 65.57 110 896 66.85 100 920 68.78
145 696 61.71 135 488 64.28 125 280 66.85 115 072 68.78 104 980 70.71
150 684 62.99 140 128 65.57 129 688 68.14 118 900 70.07 108 576 72.64
155 556 64.28 144 652 66.85 134 096 69.42 123 424 71.99 112 288 73.92
160 312 65.57 149 408 68.14 138 620 70.71 127 716 73.28 119 364 75.85
156 893 60.14 144 780 62.16 134 235 63.52 121 410 65.54 110 295 65.21
162 308 61.49 149 910 63.52 138 225 65.54 126 683 66.89 114 713 68.92
167 723 62. 16 155 325 64.87 142 500 67.57 131 100 68.92 119 558 70.95
173 423 63.52 160 883 66.22 148 628 68.92 136 230 70.27 123 975 72.30
178 980 64.87 166 440 67.57 153 900 70.27 141 360 72.30 128 963 74.33
185 108 66.22 172 140 68.92 159 315 71.62 146 063 73.65 133 380 76.35
191 093 67.57 177 698 70.27 164 730 72.98 151 620 75.68 137 940 77.71
196 935 68.92 183 540 71.62 170 288 74.33 156 893 77.03 146 633 79.73
Note: The cooling and heating capacities on the tables are in accordance with a liquid temperature increase, in the indoor exchanger, of
5° C (t = 5° C). DB = Dry bulb. RH = Relative humidity.