Watlow Series 93 Install and Wire ■ 2.1
Install and Wire
Figure 2.1a -
Series 93 Multiple
Panel Cutout
Dimensions.
Installation procedure
Bold print denotes requirement for IP65 (NEMA 4X) seal. Follow this
procedure to mount the Watlow Series 93 temperature controller:
1. Make a panel cutout using the dimensions in Figure 2.1a.
2. If your controller model number begins with 93B, make sure the
rounded side of the external case gasket is facing the panel sur-
face. Check to see that the gasket is not twisted, and is seated within the
case bezel flush with the panel. Place the case in the cutout. Make sure
the gasket is between the panel cutout and the case bezel.
NOTE:
Measurements
between panel
cutouts are the mini-
mum recommended.
Figure 2.1b-
Series 93
Dimensions.
NOTE:
For rapid mounting,
use Greenlee 1/16
DIN punch, die, draw
stud, part number
5073941.7.
2
Install and Wire the Series 93