(T13) Display: According to the operation s elected, displays the evacuation time, tank
temperature, or weightofavailable refrigerant.
STATUS AND ALARM PANEL
See Fig 7:
(C1) REPLACE FILTER: the Low side refrigerant filter/dryer m ust be changed when the led
“REPLACE FILTER”lights up.When recovering new refrigerant this light may come on
prematurely. Itmaybe reset by pres sing the SEL keywhile turning on the m achine.
(C2) HIGH PRESSURE: Lights and emits an acoustic signal when the pres sure of the fluid
in the circuit exceeds 290 psi (20 bar). The RECOVERY operation is automatically
interrupted. This will occur if you attempt to recover refrigerant with the tank valves
closed, and will require s ome disass embly to reset (see TROUBLE SHOOTING
section)
(C3) TANK FULL: Lights and em its an acous tic signal when the bottle is filled to more than
80% of maximum capacity, approximately 40 lbs. The RECOVERY operation is
automatically interrupted. You mayuse the CHARGING function to remove refrigerant
fro m the storage tan k.
(C4) LOW REFRIGERANT: Lights and emits an acous tic s ignal when the quantity of
refrigerant fluid contained in the bottle is low, near 4 lbs (~2 kg). You will need to add
additional refrigerantto continue with a CHARGING function.