Trane PKG-PRC010-EN Air Conditioner User Manual


 
29PKG-PRC010-EN
Performance
Data
Air-Cooled
15 Ton
Table PD-18. SCRB/SIRB 15 Gross Cooling Capacity
Entering Ambient Air Temperature
75°F 85°F 95°F 105°F 115°F
Airflow EDB EWB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
cf m F F MBh Mbh Mbh MBh MBh MBh MBh MBh MBh MBh
62 19011619786159101----
4800 70 67 207 91 169 106 174 77 ----
72 18011118681------
62 189 140 179 135 169 130 158 125 - -
75 67 207 115 197 110 186 105 174 101 - -
72 226 89 215 85 203 80 191 76 - -
62 189 164 179 159 169 154 159 149 - -
80 67 207 138 196 134 185 129 174 124 - -
72 226 113 215 108 203 104 191 99 - -
62 190 187 180 180 172 172 163 163 - -
85 67 207 162 196 158 185 153 174 148 - -
72 226 137 214 132 203 128 191 123 - -
62 19712520490164110----
6000 70 67 216 95 176 115 180 80 ----
72 18712019385------
62 197 154 187 149 176 144 164 139 - -
75 67 215 124 204 119 192 114 180 109 - -
72 235 93 223 88 210 84 197 79 - -
62 197 183 187 178 177 173 165 165 - -
80 67 215 152 204 148 192 143 180 138 - -
72 235 122 222 117 210 113 197 108 - -
62 202 202 193 193 184 184 175 175 - -
85 67 215 181 204 176 192 171 180 167 - -
72 234 150 222 146 210 141 197 136 - -
62 20313321093168118----
7200 70 67 222 98 180 124 185 84 ----
72 19212919789------
62 203 167 192 162 180 157 168 152 - -
75 67 221 132 209 127 197 122 185 117 - -
72 241 96 228 92 215 87 202 82 - -
62 204 200 193 193 183 183 174 174 - -
80 67 221 165 209 160 197 156 184 151 - -
72 241 130 228 125 215 120 202 116 - -
62 213 213 204 204 194 194 184 184 - -
85 67 221 199 209 194 198 189 186 183 - -
72 240 163 228 158 215 154 201 149 - -
Notes: 1. Performance based on matched air-cooled unit and remote condenser. 2. All capacities are gross and have not considered indoor fan heat. 3. CAP = total gross cooling capacity. 4. SHC =
sensible heat capacity.