PKG-PRC010-EN
Performance
Data
26
Air-Cooled
5 Ton
Table PD-15. SCRB/SIRB 5 Gross Cooling Capacity
Entering Ambient Air Temperature
75°F 85°F 95°F 105°F 115°F
Airflow EDB EWB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
cf m F F MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
62 593562275132----
1600 70 67 65 28 54 33 56 25 ----
72 57345926------
62 59 42 57 41 54 40 51 38 48 37
75 67 65 35 62 34 59 33 56 31 53 30
72 71 28 68 27 65 26 62 24 58 23
62 59 49 57 48 54 46 51 45 48 44
80 67 65 42 62 41 59 39 56 38 53 37
72 71 35 68 33 65 32 62 31 58 30
62 59 56 57 54 54 53 52 51 49 49
85 67 65 49 62 47 59 46 56 45 53 43
72 70 41 68 40 65 39 61 38 58 36
62 623865285334----
2000 70 67 67 29 56 35 58 26 ----
72 59376227------
62 62 46 59 45 56 43 53 42 50 41
75 67 67 38 65 36 62 35 58 34 55 32
72 73 29 70 28 67 27 64 25 60 24
62 61 54 59 53 56 51 53 50 50 49
80 67 67 46 64 44 62 43 58 42 55 40
72 73 37 70 36 67 35 64 33 60 32
62 62 61 60 60 57 57 55 55 52 52
85 67 67 53 64 52 61 51 58 50 55 48
72 73 45 70 44 67 42 64 41 60 40
62 634066295536----
2400 70 67 69 30 58 38 60 27 ----
72 61396328-----
62 63 49 61 48 58 47 55 45 51 44
75 67 69 40 66 38 63 37 60 36 56 34
72 75 30 72 29 69 27 65 26 61 25
62 63 59 61 57 58 56 55 54 52 52
80 67 69 49 66 48 63 46 60 45 56 44
72 75 39 72 38 69 37 65 35 61 34
62 65 65 63 63 60 60 58 58 55 55
85 67 69 58 66 57 63 56 60 54 56 53
72 75 48 72 47 69 46 65 44 61 43
Notes: 1. Performance based on matched air-cooled unit and remote condenser. 2. All capacities are gross and have not considered indoor fan heat. 3. CAP = total gross cooling capacity. 4. SHC =
sensible heat capacity.