Trane PKG-PRC010-EN Air Conditioner User Manual


 
25PKG-PRC010-EN
Performance
Data
Air-Cooled
3 Ton
Table PD-14. SCRB/SIRB 3 Gross Cooling Capacity
Entering Ambient Air Temperature
75°F 85°F 95°F 105°F 115°F
Airflow EDB EWB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
cf m F F MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
62 332035152817----
9607067 371630183114----
72 32193314------
62 33 23 32 23 30 22 28 21 26 20
75 67 37 20 35 19 33 18 31 17 29 16
72 40 16 38 15 36 14 34 14 32 13
62 33 27 31 26 30 25 28 24 26 23
80 67 36 23 35 22 33 22 31 21 29 20
72 40 20 38 19 36 18 34 17 32 16
62 33 30 31 30 30 29 28 28 26 26
85 67 36 27 35 26 33 25 31 24 29 24
72 40 23 38 22 36 22 34 21 32 20
62 352136162919----
1200 70 67 38 17 31 19 32 14 ----
72 33203415------
62 35 25 33 24 31 24 29 23 27 22
75 67 38 21 36 20 34 19 32 18 30 18
72 42 17 40 16 38 15 36 14 33 13
62 35 30 33 29 31 28 29 27 27 26
80 67 38 25 36 24 34 24 32 23 30 22
72 42 21 40 20 38 19 36 18 33 18
62 35 34 33 33 31 31 30 30 28 28
85 67 38 29 36 29 34 28 32 27 30 26
72 42 25 40 24 38 23 36 23 33 22
62 362237163020----
1440 70 67 39 17 32 21 33 15 ----
72 34213516------
62 36 27 34 26 32 25 30 24 28 24
75 67 39 22 37 21 35 20 33 20 31 19
72 43 17 41 16 39 15 37 15 34 14
62 36 32 34 31 32 30 30 29 28 28
80 67 39 27 37 26 35 25 33 24 31 23
72 43 22 41 21 39 20 37 19 34 19
62 36 36 35 35 33 33 32 32 30 30
85 67 39 32 37 31 35 30 33 29 31 28
72 43 27 41 26 39 25 37 24 34 23
Notes: 1. Performance based on matched air-cooled unit and remote condenser. 2. All capacities are gross and have not considered indoor fan heat. 3. CAP = total gross cooling capacity. 4. SHC =
sensible heat capacity.