PKG-PRC010-EN
Performance
Data
16
Fan Data
Note:
Non-standard drive selection
Oversize motor required
Oversize motor required and non-standard drive selection
Table PD-3. Fan Performance Data, 0.10 to 0.80 esp
External Static Pressure
Unit 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80
Size cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
10-Ton 3200 460 0.45 520 0.49 572 0.56 623 0.63 670 0.70 716 0.78 762 0.86 805 0.95
3600 501 0.62 558 0.67 608 0.73 653 0.80 698 0.89 741 0.97 782 1.05 823 1.14
4000 544 0.84 597 0.89 644 0.95 698 1.03 728 1.11 768 1.20 808 1.29 845 1.38
4400 586 1.10 637 1.16 682 1.22 724 1.29 763 1.38 799 1.47 836 1.57 872 1.67
4800 632 1.41 679 1.48 721 1.54 761 1.61 799 1.70 834 1.79 867 1.89 900 2.00
15-Ton 4800 478 0.77 516 0.85 555 0.95 597 1.05 634 1.17 668 1.26 700 1.34 733 1.45
5400 529 1.08 562 1.15 596 1.25 632 1.37 670 1.48 703 1.62 734 1.74 763 1.82
6000 582 1.47 611 1.53 641 1.64 672 1.76 705 1.88 739 2.01 770 2.16 798 2.31
6600 634 1.94 660 2.00 688 2.10 716 2.22 744 2.36 773 2.50 804 2.63 834 2.79
7200 688 2.51 711 2.57 736 2.66 761 2.78 787 2.92 813 3.07 840 3.22 868 3.37
10 & 15-Ton Units
Use Tables PD-3 and PD-4 with these unit configurations:
Front Return
field convertible
field convertible
clockwise horizontal
discharge
Rear Return
Front Return
standard
field convertible
field convertible
counter-clockwise
horizontal discharge
Front Return
field convertible
field convertible
clockwise vertical
discharge
Rear Return
standard
Front Return
field convertible
field convertible
clockwise vertical discharge
field convertible
counter-clockwise
horizontal discharge
Rear Return
standard