Trane PKG-PRC010-EN Air Conditioner User Manual


 
Performance
Data
Waterside
Pressure Drop
18
PKG-PRC010-EN
Chart PD-3. Waterside Pressure Drop
Pressure Drop, ft water
Condenser Flowrate, gpm
Table PD-5. Water Regulating Valve Pressure Drop, ft of water
gpm
9 101112131415161718192021222324252627282930
4.6 6.0 6.9 8.1 9.9 12.0 16.6 18.4 21.0 23.1 28.9 34.6 36.9 40.4 43.4 46.2 53.1 56.6 61.9 64.0 69.3 76.2
Note: Chart PD-3 includes factory piping and condenser. If adding a water regulating valve, add valve WPD to the
value in Chart PD-3. 10 and 15 ton units use two water regulating valves. Therefore, divide the gpm and WPD by 2 to
determine values through each valve.
Note: Table PD-5 is based on wide open water valve.