Trane PKG-PRC010-EN Air Conditioner User Manual


 
27PKG-PRC010-EN
Performance
Data
Air-Cooled
7.5 Ton
Table PD-16. SCRB/SIRB 7.5 Gross Cooling Capacity
Entering Ambient Air Temperature
75°F 85°F 95°F 105°F 115°F
Airflow EDB EWB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
cf m F F MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
62 915494417647----
2400 70 67 99 44 81 50 84 37 ----
72 86528939------
62 91 65 86 62 81 60 76 58 71 55
75 67 99 54 94 52 89 49 84 47 78 45
72 109 43 103 41 98 39 92 36 - -
62 90 75 86 72 81 70 76 68 71 65
80 67 99 64 94 62 89 60 84 57 78 55
72 108 53 03 51 98 49 92 47 - -
62 90 85 86 83 81 80 77 77 73 73
85 67 99 74 94 72 89 70 84 67 78 65
72 108 63 103 61 98 59 92 57 - -
62 955898437951----
3000 70 67 104 45 85 53 87 38 ----
72 90569341------
62 94 70 90 68 84 66 79 63 74 61
75 67 103 57 98 55 93 53 87 51 - -
72 113 44 107 42 101 40 95 38 - -
62 94 82 89 80 84 78 79 75 74 73
80 67 103 70 98 67 93 65 87 63 - -
72 113 57 107 54 101 52 95 50 - -
62 95 94 90 90 86 86 82 82 78 78
85 67 103 82 98 79 92 77 87 75 - -
72 113 69 107 67 101 64 95 62 - -
62 9761101448154----
3600 70 67 107 47 87 57 89 40 ----
72 92599542------
62 97 75 92 73 87 71 81 68 76 66
75 67 106 61 101 58 95 56 89 54 - -
72 116 46 110 44 104 41 98 39 - -
62 97 89 92 87 87 85 82 82 77 77
80 67 106 75 101 72 95 70 89 68 - -
72 116 60 110 58 104 55 98 53 - -
62 99 99 95 95 91 91 86 86 82 82
85 67 106 89 101 86 95 84 89 82 - -
72 116 74 110 71 104 69 98 67 - -
Notes: 1. Performance based on matched air-cooled unit and remote condenser. 2. All capacities are gross and have not considered indoor fan heat. 3. CAP = total gross cooling capacity. 4. SHC =
sensible heat capacity.