12-1-2. Setup to Select Function
<Procedure> Use this function while the indoor unit stops.
1
Push
SET
,
, and
buttons concurrently for 4 seconds or more.
The unit No. displayed at the first time indicates the indoor unit address of the master unit in the group control.
In this time, fan and flap of the selected indoor unit operate.
2
Every pushing button, the indoor unit numbers in the group control are displayed successively.
In this time, fan and flap of the selected indoor unit only operate.
3 Using the set temperature
/
buttons, set the item code (DN).
4
Using the timer time
/
buttons, select the setup data.
5
Push
SET
button. (OK if display goes on.)
• To change the selected indoor unit, proceed to
2
.
• To change the item to be set, proceed to
3
.
6
Pushing
button returns the status to usual stop status.
UNIT
SET
CL
UNIT No.
SET DATA
R.C. No.
4
6
1
3
5
1 2 3 4 5 6
2
END
<Operation procedure>