Toshiba RAV-SM560AT-E Air Conditioner User Manual


 
21
Indoor Unit/Outdoor Unit
RAV-SM800UT-E, RAV-SM800BT-E, RAV-SM800KRT-E/RAV-SM800AT-E
*
4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(MPa) (kg/cm²G)
Pd Ps Pd Ps
3.3 0.9 33.4 8.8
3.7 1.1 37.8 11.4
1.0 0.8 10.0 7.9
2.5 0.6 25.8 6.3
3.4 1.1 34.7 11.5
2.0 0.2 20.3 2.3
Pipe surface temperature (°C)
Discharge Suction
Indoor heat Outdoor heat
exchanger exchanger
(TD) (TS) (TC) (TE)
86 11 9 44
90 21 18 54
19448
67 6 42 2
85 23 55 16
89 16 34 18
Compressor
revolutions per
second (rps)
*
64
52
27
65
31
90
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor Outdoor
27/19 35/
32/24 43/
18/15.5 5/
20/ 7/6
30. 24/18
15/––20/
(70%)
Indoor unit
Outdoor unit
Outer diameter of refrigerant pipe
Gas side ØA Liquid side ØB
15.9mm 9.5mm
TCJ
sensor
Air heat exchanger
Strainer
Strainer
TC sensor
Refrigerant pipe
at liquid side
Outer dia. ØB
Refrigerant pipe
at gas side
Outer dia. ØA
Packed valve
Outer dia. ØB
Packed valve
Outer dia. ØA
Max
50m
TS sensor
Accumulator
(1500cc)
TD sensor
TO sensor
TE
sensor
4-way valve
(STF-0213Z)
Ø25 × L160
Rotary compressor
(DA220A2F-20L)
Heat exchangerØ8
1 row 30 stages
FP1.3 flat fin
Modulating (PMV)
(SKV-18D26)
Capillary
Ø3×Ø2×
L530
Ø25 × L210
Muffler
R410A 1.5 kg
Cooling
Heating
Ps
Pd