Toshiba RAV-SM560AT-E Air Conditioner User Manual


 
142
15-2. Replacement of Distributor Assembly
RAV-SM560UT-E
1. Cutting of Capillary Tube
A capillary tube ( 023 : Inner diameter 2mm, Length 1000mm) is brazed to a distributor assembly. Cut and
divide the tube to each length as shown below.
NOTE) Break off the capillary tube so
that inner diameter is not deformed
Ref No.
023
No. of capillary tubes
4
Cutting
200 mm : 2 pcs.
400 mm : 2 pcs.
[Cutting]
Plane circumference of the capillary tube with
triangle file, etc., and then break off it.
2. Attachment of joint pipe
Insert the attached joint pipe into the end of the
capillary tube up to 15mm, and braze it.
Form the capillary tube as same as that in the
distributor assembly before replacement.
3. Brazing to indoor heat exchanger
Attach the capillary tube processed in items 1 and 2 to the end of the pipe with brazing as shown below.
023