– 151 –
[Mounting]
In case of AIK-PXXXH series
1. As same as P.C. board before replacement, attach a cable (Black) which is screwed to the electric parts
box to CN240 without using a cable (Black) attached previously to CN240 of the service P.C. board.
Service P.C. board
Cable
(Remove a cable
attached previously
to CN240 of the
service P.C. board.)
CN204
2. Attach other cables as same as P.C. board before replacement.
Part name
SW03
1
2
Function
TA shift: Thermo-OFF point can be shifted in heating operation.
Bit 1 Bit 2
OFF OFF
OFF ON
ON OFF
ON ON
Shift Q’ty
+ 6K
+ 4K
+ 2K (Setup at shipment)
± 0K
Selection of hot start control temperature :
The starting temperature of the fan can be raised in heating operation.
J09
Provided
None
Setup
Normal (Setup at shipment)
Fan starting temp up (Approx. +4K)
Setup of filter timer
J11 J12
Provided Provided
None Provided
Provided None
None None
Setup
240 hours (Setup at shipment)
2500 hours
5000 hours
Without filter timer
J09
J11
J12
<(Reference) Explanation about functions of switches/jumpers>
• The following table shows the functions of the main switches and jumpers. Use as reference in miss-setup.