– 17 –
1-2. Outdoor Unit
<Digital Inverter>
Model name RAV-
Power supply
Type
Compressor Motor (kW)
Pole
Refrigerant charged (kg)
Refrigerant control
Standard length (m)
Min. length (m)
Max. total length (m)
Inter connecting pipe
Additional refrigerant charge
under long piping connector
Height
Outdoor lower (m)
difference
Outdoor higher (m)
Height (mm)
Outer dimension Width (mm)
Depth (mm)
Appearance
Total weight (kg)
Heat exchanger
Fan
Fan unit Standard air flow (m³/h)
Motor (W)
Connecting pipe
Gas side (mm)
Liquid side (mm)
Sound pressure level Cooling/Heating (dB•A)
Sound power level Cooling/Heating (dB•A)
Outside air temperature, Cooling (°C)
Outside air temperature, Heating (°C)
SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E
1 phase 230V (220 – 240V)
50Hz (Power exclusive to outdoor is required.)
Hermetic compressor
1.1 1.6 2.5 3.0
4444
1.0 1.7 2.8 2.8
Pulse motor valve
7.5 7.5 7.5 7.5
5.0 5.0 5.0 5.0
30 30 50 50
20g/m 40g/m 40g/m 40g/m
(21m to 30m) (21m to 30m) (31m to 50m) (31m to 50m)
30 30 30 30
30 30 30 30
550 550 795 795
780 780 900 900
290 290 320 320
Silky shade (Muncel 1Y8.5/0.5)
38 42 77 77
Finned tube
Propeller fan
40 45 75 75
43 43 100 100
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5
46/48 48/50 53/54 53/54
63/65 65/67 70/71 70/71
43 to –15