– 117 –
(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
Line address
1
Indoor unit address 1
Group address 1
For the above example, perform setting by connecting
singly the wired remote controller without remote
controller inter-unit cable.
Group address
Individual : 0000
Master unit : 0001
Sub unit : 0002
In case of group control
OUT
IN
OUT
IN
2
1
2
1 2 3 4 5 6 7 8 9 10 11
END
<Operation procedure>
1
3, 6, 9
END
11
2, 5, 8
4, 7, 10
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
UNIT No.
DATA
SET
R.C. No.
13-3. Address Setup
In case th at addresses of th e indoor units will be determined prior to piping work after cabling work
(Manual setting from remote controller)
<Address setup procedure>
• Set an indoor unit per a remote controller.
• Turn on power supply.
1 Push
SET
+
CL
+
TEST
buttons simultaneously
for 4 seconds or more.
2 (
←←
←←
← Line address)
Using th e temperature setup
/ buttons,
set
12 to th e item code.
3 Using timer time / buttons, set th e line address.
4 Push
SET
button. (OK when display goes on.)
5 (
←←
←←
← Indoor unit address)
Using th e temperature setup
/ buttons,
set
13 to th e item code.
6 Using timer time / buttons, set 1 to th e line address.
7 Push
SET
button. (OK when display goes on.)
8 (
←←
←←
← Group address)
Using th e temperature setup
/ buttons,
set
14 to th e item code.
9 Using timer time / buttons, set 0000 to Individual,
0001 to Master unit, and 0002 to sub unit.
10 Push
SET
button. (OK when display goes on.)
11 Push
TEST
button.
Setup completes. (The status returns to the usual stop status.)