Toshiba RAV-SM1402CT-E Air Conditioner User Manual


 
118
1 2
END
Operation
<Operation procedure>
2
1
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
UNIT No.
1 2 3
END
<Operation procedure>
3
1
2
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
UNIT No.
DATA
SET
R.C. No.
n Confirmation of indoor unit No. position
1. To k now th e indoor unit addresses th ough position of th e indoor unit body is recognized
In case of individual operation (Wired remote controller : indoor unit = 1 : 1)
(Follow to the procedure during operation)
<Procedure>
1 Push
ON / OFF
button if th e unit stops.
2 Push
UNIT
button.
Unit No. 1-1 is displayed on LCD.
(It disappears after several seconds.)
The displayed unit No. indicate line address and
indoor unit address.
(When other indoor units are connected to the
identical remote controller (Group control unit), other
unit numbers are also displayed every pushing
UNIT
button.
2. To k now th e position of indoor unit body by address
To confirm the unit No. in the group control
(Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.)
<Procedure>
The indoor unit numbers in the group control are succes-
sively displayed, and fan, louver, and drain pump of the
corresponding indoor unit are turned on.
(Follow to the procedure during operation)
1 Push
VENT
and
TEST
buttons simultaneously for
4 seconds or more.
Unit No. ALL is displayed.
Fans and louvers of all the indoor units in the
group control operate.
2 Every push ing
UNIT
button, th e unit numbers
in th e group control are successively dis-
play ed.
The unit No. displayed at the first time indicates the
master unit address.
Fan and louver of the selected indoor unit only
operate.
3 Push
TEST
button to finish th e procedure.
All th e indoor units in th e group control stop.