8-4. Freeze Prevention (Cooling)
●
This function prevents freezing of the indoor heat exchange coil.
●
When the compressor has been running for 10 minutes or more and the temperature of the indoor heat
exchange coil falls below 30°F, the control circuit stops the compressor for at least 6 minutes. The compressor
does not start again until the temperature rises above 46°F or 6 minutes has elapsed.
8-5. Overload Prevention (Heating)
●
This function prevents overheating of the indoor heat exchange coil.
●
When the temperature of the indoor heat exchange coil rises above 139°F, and if the indoor fan is L (low
speed), then the fan speed changes from L (low speed) to M (medium speed).
●
When the temperature of the indoor heat exchange coil rises above 141°F, the outdoor fan stops.