Roberts Gorden 10081601NA Rev H 12/11 Heating System User Manual


 
SECTION 8: COMMISSIONING THE CORAYVAC
®
SYSTEM
47 of 62
Step 8.1.3 After setting end vent vacuums between
2.5" wc and 3.0" wc, while all the burners are still
operating, use the down arrow button on the VFD to
reduce the frequency of the output signal to the
pump. Reduce the frequency of the VFD until the
manometer at each of the end vents reads 1.0" wc -
1. 2 " wc, Make note of this frequency setting below.
The frequency is found on the VFD’s LCD screen.
1.0" w.c. - 1.2" wc VFD Frequency Setting
Step 8.1.4 Retu rn to the PC and click the pump and
zones to "OFF".
Step 8.1.5 Using the procedure described on Page
42, Section 7.1.1 through Section 7.1.5, alter the fol-
lowing parameters on the VFD:Return to the PC and
click the vacuum pump and three zones to "AUTO",
then click exit.
Parameter
Number
Parameter
Name
Factory
Default
New
Setting
P01 Line Voltage 01 01
P03 Start Method 01 05
P05 Standard
Speed
Source
01 (03) (0-10) Vdc
(04) (4-20) mA
P44 Password 225 Any #
000-999
P45 Speed at
Minimum
Signal
0.0Hz Frequency
Setting noted
on Page 44,
Section 8.1.2
P46 Speed at
Maximum
Signal
60.0Hz Frequency
Setting noted
on Page 44,
Section 8.1.2
Record Frequency Setting Here: