Roberts Gorden 10081601NA Rev H 12/11 Heating System User Manual


 
SECTION 7: VARIABLE FREQUENCY DRIVE PROGRAMMING
43 of 62
the password must be entered in order to access the
parameters again.
7. 2 A l t e r i n g VFD Parameters
Using the procedure described on Page 42, Section
7.1.1 through Section 7.1.5, alter the following parame-
ters:
Parameter
Number
Parameter
Name
Factory
Default
New
Setting
P01 Line Voltage 01 01
P03 Start Method 01 05
P05 Standard
Speed
Source
01 (03) (0-10) Vdc
(04) (4-20) mA
P44 Password 225 Any #
000-999
P45 Speed at
Minimum
Signal
0.0Hz Frequency
Setting noted
on Page 44,
Section 8.1.2
P46 Speed at
Maximum
Signal
60.0Hz Frequency
Setting noted
on Page 44,
Section 8.1.2