Regency P121LC Indoor Fireplace User Manual


 
Regency
®
P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace 13
INSTALLATION
EXTERIOR VENT TERMINATION LOCATIONS
A= Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm)
B= Clearance to window or door that may be opened *(12"/30cm) #(9"/23cm)
C= Clearance to permanently closed window *(min. 12"/30cm)
D= Vertical clearance to ventilated soffi t located above the terminal within a horizontal
distance of (24"/60cm) from the centerline of the terminal (min. 18"/46cm) check with
local code.
E= Clearance to unventilated soffi t (min. 20"/51cm)
F= Clearance to outside corner: with AstroCap Termination Cap (min 6"/15cm), with Dura-
Vent Termination Cap (14"/36cm)
G= Clearance to inside corner: with AstroCap Termination Cap (min 6"/15cm), with Dura-
Vent Termination Cap (12"/30cm)
H= Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally
from the centerline of the regulator.
J= Clearance to service regulator vent outlet *(min 36"/90cm)
K= Clearance to non-mechanical air supply inlet to building or the combustion air inlet to
any other appliance *(12"/30cm) #(9"/23cm)
L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m)
#3' (91cm) above if within 10' (3m) horizontally.
M= Clearance above paved sidewalk or a paved driveway located on public property
*(min. 84"/2.1m)
N= Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)
Note:
- A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
- Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
- If the vent termination is accessible, a certifi ed guard shall be installed.
* As specifi ed in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.
# In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
B
A
G
M
24”
A
A
B
A
C
Fixed Closed
Openable
Openable
D
E
A
K
B
F
Fixed Closed
H
24”
18”
L
N
J
Vent Termination
A
AirSupplyOutlet
Areawhereterminalisnotpermitted
Do
this
Never
dothis
2ft.
(600mm)
B-Vent Only:
Ifvent
isless
than
10ft.
(3m)
from
wall-locate
raincapnotless
than
2ft.(600mm)
above
wall.
Feet Meters
Minimum
V
entHeight
Roof
Pitch
over
7/12
to8/12
over
8/12
to9/12
over
9/12
to10/12
over
10/12
to1
1/12
over
1
1/12
to12/12
over
12/12
to14/12
over
14/12
to16/12
over
16/12
to18/12
over
18/12
to20/12
over
20/12
to21/12
flat
to7/12
0.61
0.61
0.61
0.76
0.99
1.22
1.52
1.83
2.13
2.29
2.44
2
2
2
2.5
3.25
4
5
6
7
7.5
8