Regency P121 Indoor Fireplace User Manual


 
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace 11
VENTING
INTRODUCTION
The P121-1/P121LC-1/P121RC-1/P131-1 uses
the "balanced flue" technology Co Axial
system. The inner liner vents products of com-
bustion to the outside while the outer liner
draws outside combustion air into the combus-
tion chamber thereby eliminating the need to use
heated room air for combustion and losing
warm room air up the chimney.
Note: These flue pipes must not be con-
nected to any other appliance.
The gas appliance and vent system must be
vented directly to the outside of the building, and
never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Each direct vent gas appliance must use it's
own separate vent system. Common vent sys-
tems are prohibited.
INSTALLATION
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The 4 Top Standoffs must be correctly positioned and attached to the top before unit is slipped
into position.
Top Standoff Assembly
The top standoffs are shipped in a flat position and must be folded into shape and attached.
1) Remove the standoffs from the fireplace
top.
2) Take each standoff and bend into the
correct shape. Bend up at the bend lines
until the screw holes in the standoff and the
pre-punched screw holes on the fireplace
top line up.
3) Attach the standoff securely to the top with
4 screws per standoff (on opposite cor-
ners).
FACING & FINISHING REQUIREMENTS
This fireplace is supplied with a 3" metal extension trim above the fireplace. The extension trim may be replaced if the framing is faced with a non-
combustible material placed flush with the front and side face of the unit and extending from the top of the unit. (ie. tile, slate, etc.)