Regency HZ54 Indoor Fireplace User Manual


 
HZ54 Regency Horizon
TM
Gas Fireplace 25
INSTALLATION
Vent must be supported at offsets.
Firestops are required at each oor level and
whenever passing through a wall.
Maintain clearances to combustibles as listed in
the "Clearances" section.
Refer to the "Vent Restrictor Position" section
for details on how to change the vent restrictor
from the factory setting of Set 1 to Set 3 or Set 4
if required.
Note: Must use optional ue adaptor when using
Rigid Pipe (Part # 770-994).
INSTALLATION
Maximum: 40 ft. (12.2m)
Minimum
8’6” (2.6m)
Min. 44”
(1118mm)
Max. 10’ (3m)(centerline to centerline)
Maximum: 27 ft. (8.2m)
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
Vertical Height (Feet)
32
34
36
38
6
8
Horizontal (Feet)
2
0
4
10 12
12 16
18
14
20
Vent Restrictor on Set 3
Vent Restrictor on Set 4
Vent Restrictor on Set 1
Minimum length of pipe
between elbows 12” (305mm)
VENTING ARRANGEMENTS
ALLOWABLE VERTICAL TERMINATIONS FOR HZ54-LP
The shaded area in the diagram shows all allowable
combinations of straight vertical and offset to vertical
terminations, using two 90
o
elbows, with Rigid Pipe Venting
Systems for Natural Gas. Two 45
o
elbows equal to one 90
o
elbow. Maximum of four 45
o
elbows allowed.
Please note min. 1 foot between 90
o
elbows is required.