Quadra-Fire 5100I-GD-B Indoor Fireplace User Manual


 

5100-I ACT WOOD INSERT
R
438-0380E
April 21, 2010
Hearth Extension
A
B
C
F
E
Insert
SideWall
Fascia or Trim
Mantel
D
Maximum Mantel Depth: 12 inches (305mm)
B. Clearance to Combustibles
C. Optional Mantel Deector
       
dealer to reduce clearances to a mantel. An 8 inch (203mm)

-ANTELDEFLECTOR
Figure 9.1
Comply with all minimum clearances to

 
WARNING

Minimum Clearances To Combustible Material
With 8 inch (203mm)
Mantel Deflector
35"/889mm
16"/406mm
C
7"/178mm
7"/178mm
D
CANADA
40"/1015mm
27"/686mm
12"/305mm
12"/305mm
USA
8"/200mm
8"/200mm
F
16"/406mm
18"/450mm
E
FLOOR PROTECTION
*Zero Clearance Installations USA Only
Masonry, Heat Exchanger
& *Zero Clearance
BA
Side Trim
Top Trim
1-1/2” (38mm) thick
3/4” (19mm) thick
TRIM
Maximum Mantel Depth
12”/305mm
       

material.
    
-
als (i.e., plastics, wood paper products, etc.) are combustible

some form of thermal designation such as R-value (thermal
D. Floor Protection USA & Canada
E.
Calculating Alternate Floor Protection
Material
Thermal Conductivity: k value
 
      


means less heat is being conducted through the non-combus-
         

  
(foot
2
(hour) (
o

Thermal Resistance: R value

transfer. R value is convenient when more than one material
is used since you can add the R values together, whereas you

less heat is being conducted through the non-combustible ma-


be acceptable.
Converting k to R:
      
inches of the material.

Converting R to k:


Calculatons:




0.84 and therefore is acceptable.