18. POSITIONING OF THE IGNITION AND FLAME SENSING ELECTRODE
To measure the performance of combustion products, the forced draught boiler models are equipped with two
test points on the tapered coupling specically designed for this purpose.
One of the two test points is connected to the exhaust ue duct to allow measurements of the combustion
products and efciency.
The second test point is connected to the comburant air inlet duct to check possible combustion products
circulation in case of coaxial ducts.
The exhaust ue duct test point allows measurements of the following:
• combustionproductstemperature;
• concentrationofoxygen(O
2
) or, alternatively, of carbon dioxide (CO
2
);
• concentrationofcarbonmonoxide(CO).
The comburant air temperature must be measured at the test point connected to the air inlet duct.
19. CHECK OF COMBUSTION PARAMETERS