Concentric flue
This type of duct allows to emit exhaust gases and to draw combustion air from outside the building.
The 87° coaxial bend allows to connect the boiler to a ue-air duct in any direction as it can rotate through
360°.
If the ue outlet is placed outside, the ue-air ducting must protrude at least 18mm out of the wall to allow
alluminium weathering tile to be tted and sealed to avoid water leakages. If the terminal is below 2m then a
terminal gaurd is required.
Ensure a minimum downward slope of 3° towards the boiler.
A 87° bend reduces the total ue length by 1 metre.
A 45° bend reduces the total ue length by 0.5 metre.
HORIZONTAL CONCENTRIC FLUES
Boiler Flue Size
Number of Bends 90°
1 2 3 4
WH46 Ø80/125 9 m 8 m 7 m 6 m
WH65 Ø80/125 9 m 8 m 7 m 6 m
VERTICAL CONCENTRIC FLUES
Boiler Flue Size
Number of Bends 90°
1 2 3 4
WH46 Ø80/125 9 m 8 m 7 m 6 m
WH65 Ø80/125 9 m 8 m 7 m 6 m
CONVENTIONAL FLUE
Boiler Flue Size
Number of Bends 90°
1 2 3 4
WH46 Ø80 59,5 m 59 m 58,5 m 58 m
WH65 Ø80 59,5 m 59 m 58,5 m 58 m
Figure 8
990519_0400
Concentric outlet