Airflow direction, Fan speed and Setting temperature are
optimized.
•
• •
•
“[Intake Air temperature] - [Remote controller setting
temperature]” is detected every 30 seconds by indication
from indoor unit and controlled to each area.
Quick Heating
→
Unit forcibly turns to Quick Heating operation
for 5 minutes after Powerful-ON even through it is in the Warm
Heating area.Warm Heating
→
Discharge air temperature is
kept high by changing fan speed according to room
temperature and warm feeling will be produced.
9.7.3. Heating Operation
9.8. Automatic Operation
•
• •
•
Operation mode (Cooling, Dry and Heating) is automatically selected.
•
• •
•
Operation mode is selected at the beginning of unit operation and every 30 minutes. Temperature, fan speed and airflow
direction are set with the remote controller.
•
• •
•
During cooling mode operation, if Dry mode is selected in next operation mode selection, the operation will be Cooling Dry.
9.8.1. Operation Mode Selection
Operation mode is selected according to outdoor air temperature, intake air temperature and setting temperature.
1. "Heating" is selected when outdoor air temperature is below 16°C.
2. "Cooling" is selected when intake air temperature is 25°C or more. (But, when intake air temperature is 16°C or more.)
3. When outdoor air temperature is below 25°C, if remote controller setting temperature is increased, selectable range of
“Heating”, if decreased, selectable range of “Heating” will be extended respectively.