Panasonic CS-HE9DKE Air Conditioner User Manual


 
Table (b): Outdoor Air Temperature Shifting
Mode: Outdoor Temperature, X (°C): Temperature Shift (°C)
CS-HE9DKE CS-HE12DKE
Cooling/Soft Dry 38 X 0.00 0.00
30 X 38 0.00 0.00
23 X 30 0.00 0.00
X 23 0.00 0.00
Heating 21 X 0.00 0.00
17 X 21 0.00 0.00
9 X 17 0.00 0.00
5 X 9 +0.50 +1.00
1 X 5 +1.00 +1.25
X 1 +1.50 +2.00
Table (c): Fan Speed Shifting
Mode: Fan Speed: Temperature Shift (°C)
Cooling All +1.25
Soft Dry All +1.0
Heating Lo +1.0
Hi, Me-, Me, Me+, Auto +0.25 (CS-HE9DKE)
+0.50 (CS-HE12DKE)
Table (d): Start-Up Shifting
Mode within 60 Minutes from Start-up: Temperature Shift (°C)
Cooling/Soft Dry -1.0
Heating +2.0
9.2. Indoor Power Relay Control
The Power Relay turns on under the following conditions.
1. For three minutes, when plugged in the A/C or the Error Reset button on remote controller is pressed.
2. During Installation Check Mode and following for three minutes after checking.
3. During On-timer sampling and during Preliminary operation.
4. During Operation and following for three minutes after the operation is stopped.
5. During Auto Operation, Test run, Forced Heating or Odour Removal Operation and following for three minutes after the
operation is stopped.
21
CS-HE9DKE CU-HE9DKE / CS-HE12DKE CU-HE12DKE