Orbit Manufacturing ORBIT-6 RP-206 Smoke Alarm User Manual


 
Installer Manual
23
Location: 26 Dialer Controls: (2
nd
Digit):
2
nd
Digit Attempts Answering Machine UL Installation Voice Module
0 3 No No No
1 8 No No No
2 3 Yes No No
3
(default)
8 Yes No No
4 3 No Yes No
5 8 No Yes No
6 3 Yes Yes No
7 8 Yes Yes No
8 3 No No Yes
9 8 No No Yes
A 3 Yes No Yes
B 8 Yes No Yes
C 3 No Yes Yes
D 8 No Yes Yes
E 3 Yes Yes Yes
F 8 Yes Yes Yes
Central Station Protocols: Location 27-28
Format Name
(PPS)
pulses/sec
Kissoff/
Handshake
Validation
InterDigit
Time
Code
format
Silent Knight/
ADEMCO Slow
10 1400Hz Dual round 650 0F
Silent Knight/
ADEMCO Slow Extended
10 1400Hz Dual round 650 4F
Radionics/DCI/ Franklin slow 10 2300 Hz Dual round 650 17
Silent Knight Fast 20 1400 Hz Dual round 650 0E
Silent Knight Fast Extended 20 1400 Hz Dual round 650 4E
Sescoa/Franklin/Vertix/ DCI fast 20 2300Hz Dual round 650 16
Sescoa/Franklin/Vertix/DCI
Extended
20 2300Hz Dual round 650 56
Universal high speed 20 2300Hz Dual round 390 12
Radionics 20 1400 Hz Dual round 390 02
Radionics 20 2300Hz Dual round 390 12
Radionics Extended 20 1400 Hz Dual round 390 42
Radionics Extended 20 2300Hz Dual round 390 52
Radionics 40 1400 Hz Dual round 390 00
Radionics 40 2300Hz Dual round 390 10
Radionics Extended 40 1400 Hz Dual round 390 40
Radionics Extended 40 2300Hz Dual round 390 50
Radionics 40 1400 Hz Parity 390 20
Radionics 40 2300Hz Parity 390 30
Radionics Extended 40 1400 Hz Parity 390 60
Radionics Extended 40 2300Hz Parity 390 70
Example: to use ADEMCO slow enter 0F to location 27