Orbit Manufacturing ORBIT-6 RP-206 Smoke Alarm User Manual


 
Installer Manual
18
Locations: 14-21 Zone 1-8: (2
nd
Digit): Sound Default:
2
nd
Digit Zone Sound and Comments
0
Silent
a violation during the armed period will produce no sound
the resulting alarm can still be reported to the Central Station
1
(default)
External Sounder (Continuous)
causes the external sounding device to annunciate steadily, without breaks in the
sound cadence the sound will continue until the sounder “times out” or the system is
disarmed
2
External Sounder (Pulses)
causes the external sounding device to produce a pulsed (or staggered) annunciation
this sound is usually recommended for fire alarm annunciation
3
Keypad Sounder Only
causes the piezo sounder within the system’s keypad(s) (only) to beep rapidly
4
External Sounder + Keypad Sounder
causes the external sounding device to annunciate continuously, without breaks in the
sound cadence causes the piezo sounder within the system’s keypad(s) to beep rapidly
5
External Sounder When Armed / Keypad Sounder When Disarmed
related to 24H zones
when alarm during disarm, the keypad’s buzzer will be activated
when alarm during armed system, the external sounder will be activated
6
Door Chime
assigned to an opening which, when violated during the disarmed period, will cause the
system’s keypad(s) to beep once during an alarm, the external sounding device will
annunciate continuously, without interruption. When alarm occurs during armed system
only the external sounder will be activated.
Zone Location Type Sound
Z1 14 (3) (1)
Z2 15 (5) (1)
Z3 16 (2) (1)
Z4 17 (6) (1)
Z5 18 (2) (1)
Z6 19 (2) (1)
Z7 20 (0) (0)
Z8 21 (0) (0)
* (x) define the type and sound default
SPECIAL ZONE TYPES:
Location: 18 Zone 5: Fire Zone
Zone 5 is reserved as a Fire Zone, supports four-wire Smoke Detectors. Smoke
Detector power must be interruptible in order to reset a detector “latched” in alarm. As
such it should be derived from the UO/ECL or one of the UOs terminal (see Figures 1A
and 1B). The related UO should be defined as AUX power switch.
Location: 18 Zone 5: (1
st
Digit): Type Default: Fire
1
st
Digit Zone Type and Comments
7
Fire
A fire zone cannot be disabled or bypassed.
A fault in the wiring to the zone will cause a Fire Trouble (fire LED blinks).
A short in the zone wiring will cause a fire alarm.