L NAPCO Security Systems
X GEM-P1664 Installation Instructions
WI1424A 1/06
Page 35
Zone will go into an instant alarm. If the panel is armed with the entry delays canceled (Instant protection), any violation on the Exit/
Entry Zone or the Exit/Entry Follower Zone will cause an immediate alarm.
Exit Time Restart
This option allows for the following scenario prior to the end of the Exit Time: a violation of an entry/exit zone, a restore, and a sec-
ond violation of an entry/exit zone restarts the Exit Time. The panel does not allow the Exit Time to be restarted more than once.
The default setting for this option is enabled.
Expansion Module Zones; EZM Type; EZM Tamper See Tamper
Zones 9–64 or 17-64 (with "Zone Doubling" enabled) are expansion zones added to the basic system using expansion zone modules
(EZMs). Any combination of GEM-EZM8 (8 zones) and/or the 4-zone EZM modules integral to each GEM-RP1CAe2 keypad may be
used. Refer to the instructions accompanying each module for wiring information.
Each GEM-EZM4/8 Zone Expansion Module has series zone doubling and supervision capability. When an EZM is selected for zone
doubling, the EZM will respond as EZM 1 (zones 17 to 24) or EZM 3 (zones 25 to 32) when polled. (Refer to GEM-EZM4/8 Installa-
tion Instructions). The EZM zone doubling or loop supervision functionality can be set to either follow the panel configuration or to act
as a standard non-zone doubled EZM. Program (see Programming Instructions) to enable all EZM's to follow the attributes of the
control panel (global panel feature). Note: A GEM-EZM8 cannot be used if the panel is set for loop supervision or zone doubling
and this feature is enabled.
Regardless of how the modules are arranged, the expansion zones are divided into consecutively-numbered groups of four. Each 8-
zone module comprises two groups. Each group is assigned a number.
EZ Arming (Easy Arming); Easy Arming Closing Report
Permits quick arming by simply pressing the
D button for "Classic" RP Style keypads. Each keypad may be individually
programmed for Easy Arming (see Keypad Features). Disarming still requires entry of a valid user code. NOTE: Do not program in
UL installations. If closings are reported, Easy Arming will report as User 67. Press and hold P or Q to EZ Arm "K Se-
ries" keypads.
EZ Zone Doubling
The control panel zone configuration may be expanded from 8 to 16 zones without the use of EZM Modules. To do so simply select
"Zone Doubling" and connect zones as shown in Wiring Diagram. The 3.9K EOL resistor must be placed at the end of the loop of the
higher zone. For proper supervision, the 2.2K EOL resistor must be placed at the end of the loop of the lower zone.
Note: If Zone Doubling is to be used, then normally closed devices must be wired to both zones. If Normally open zones for fire or
panic devices are required, then the lower zone (2.2K EOL resistor) must be used and the higher zone (3.9K EOL resistor) must not
be programmed for any area.
Fire; Keypad Fire
Any zone may be programmed for Fire. Connect normally-open devices across a Fire Zone. (The EOL2.2K end-of-line resistor must
be installed). A short across the zone will cause a fire alarm, which will be indicated at the keypad by a "
FIRE ALARM" LCD display and
pulsing sounder. An open circuit on the Fire Zone will identify a trouble and cause flashing "SYSTEM TROUBLE/E41-00 SERVICE" LCD
display and pulsing sounder after a 10-second delay. The sounder may be silenced by pressing the
C button. The LED will go
off within 30 seconds after reset if the alarm or trouble is cleared. For Smoke-Detector Reset, see Alarm Outputs. Fire or Keypad
Fire can be made to trip an alarm or report to Central Station. If Keypad Fire is programmed, pressing both the
7 and G
buttons at the same time will sound a fire panic alarm and display "FIRE ALARM" at the keypad. The Keypad Fire function is
supplementary to the hardwired zones. Note: This feature shall not be considered a substitute for listed manual initiating devices. A
fire condition that has not been restored will cause the zone number and description to scroll. To reset (acknowledge) the condition,
enter a valid code, then press the
U button.
Fire Verification (Not for use in California)
An alarm on any Fire Zone programmed for "Fire Verification" and connected to the fire power terminal will cause all fire zones to be
powered down for 12 seconds. (All devices must be wired with + power on Terminal 25). After this time, power is restored and a 4-
second power-up time is started. Thereafter, the zone will be active again. This represents a total processing delay of 16 seconds
from the time the alarm is first detected. If an alarm condition still exists at this time or reoccurs within 2 minutes, an alarm will be
initiated, otherwise the zone will return to its original state. Note: A zone programmed for "Fire Verification" must be programmed as
a "Fire Zone" as well.
GEM-Print
A printer can be made to print all logged operations directly from the panel, when programmed for "Enable GEM-PRINT Module" and
a separate Gem-Print Module is added to the panel.
Include Selective Bypass In Conditional Closing/Status See Closing Report.
Glossary