3
8
8.2
[Fig. 8.2.1]
B
A
A
B C D
e
a
No.1
No.2 No.3 No.4
No.5
b c d
C
C
CCC
B
A
a
b
c d e
C
D
CC
CC
A
No.1 No.2
No.3 No.4 No.5
A: Outdoor unit
B: First branch
C: Indoor unit
D: Cap
7
[Fig. 7.1.1]
B
A
A: M10 anchor bolt procured at the site.
B: Corner is not seated.
A (Unit : mm [in])
B, C, D (Unit : mm [in])
a, b, c, d, e (Unit : mm [in])
Ï Downstream unit model total
~ 72
73 ~ 144
145 ~ 234
Ó The 1st branch of P168 ~ P234
235 ~
Ì Branch kit model
CMY-Y102S-G
CMY-Y102L-G1
CMY-Y202-G1
CMY-Y302-G1
Å Outdoor model
P72
P96
P108
P126
P144
P168
P192
P204
P216
P234
ı Liquid pipe
ø9.52 [3/8]
*1 ø9.52 [3/8]
*2 ø9.52 [3/8]
ø12.7 [1/2]
ø12.7 [1/2]
ø15.88 [5/8]
ø15.88 [5/8]
ø15.88 [5/8]
ø15.88 [5/8]
ø15.88 [5/8]
Ç Gas pipe
ø19.05 [3/4]
ø22.2 [7/8]
ø22.2 [7/8]
ø28.58 [1-1/8]
ø28.58 [1-1/8]
ø28.58 [1-1/8]
ø28.58 [1-1/8]
ø28.58 [1-1/8]
ø28.58 [1-1/8]
ø28.58 [1-1/8]
Î Total capacity of indoor units
~ 54
55 ~ 72
73 ~ 108
109 ~ 144
145 ~ 234
235 ~ 288
289 ~
ı Liquid pipe
ø9.52 [3/8]
ø9.52 [3/8]
ø9.52 [3/8]
ø12.7 [1/2]
ø15.88 [5/8]
ø19.05 [3/4]
ø19.05 [3/4]
Ç Gas pipe
ø15.88 [5/8]
ø19.05 [3/4]
ø22.2 [7/8]
ø28.58 [1-1/8]
ø28.58 [1-1/8]
ø28.58 [1-1/8]
ø28.58 [1-1/8]
Model number
06,08,12,15,18
24,27,30,36,48,54
72
96
ı Liquid pipe
ø6.35 [1/4]
ø9.52 [3/8]
ø9.52 [3/8]
ø9.52 [3/8]
Ç Gas pipe
ø12.7 [1/2]
ø15.88 [5/8]
ø19.05 [3/4]
ø22.2 [7/8]
¬ 4-Branching header
(Downstream unit
model total
<
=
72)
CMY-Y104-G
Ô 8-Branching header
(Downstream unit
model total
<
=
144)
CMY-Y108-G
˚
10-Branching header
Downstream unit
model total
<
=
234)
CMY-Y1010-G
*1 ø12.7 [1/2] for over 90m [295ft]
*2 ø12.7 [1/2] for over 40m [131ft]
[Fig. 8.2.2]