Mitsubishi Electronics PURY-P144 Air Conditioner User Manual


 
[ IX Troubleshooting ]
- 320 -
HWE0803A GB
(2) Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement procedures
Remove the Solenoid valve block ASSY following "(1) Solenoid valve block ASSY (SV4a, SV4b, SV4d) replacement
procedures" on the front page.
Debraze H-M parts (total 6 places), and remove the Check valve ASSY.
Replace the Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) to be serviced while it is removed from the unit.
Braze the pipes as they were according to the angle of the pipes on the next page (Figure as viewed from point Q).
Mount the solenoid valve block ASSY, coil cover, and peripheral cables back in place according to "(1) Solenoid valve
block ASSY (SV4a, SV4b, SV4d) replacement procedures" on the front page.
H
(φ19.05 [3/4"])
I
(φ15.88 [5/8"])
Heat exchanger
J
(φ12.7 [1/2"])
K
(φ6.35 [1/4"])
* After removing Solenoid valve block ASSY
Part A (Refer to the next page.)
* Precautions for replacing Check valve
Be sure to perform no-oxidation brazing when brazing.
Place a wet towel on the check valve when heating pipes to keep the temperature of the valve from exceed-
ing 120°C [248°F].
After brazing, check the condition around the brazing. After confirming no leakage, evacuate the air
inside. (*1)
Perform carefully with the flame direction so that it does not burn cables and plates etc. in the unit.
Remove the brazing part protecting heat exchanger fins not to be burn, and replace the service parts.
*1: Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.