Mitsubishi Electronics PURY-P144 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 168 -
HWE0803A GB
Operation
Outdoor unit model
PURY-P168TSHMU-A
PURY-P96THMU-A PURY-P72THMU-A
Model name of BC controller CMB-P108NU-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor 35°C/- [95°F/-]
Indoor unit
No. of connected units
Unit
5
No. of units in operation 5
Model - 30/30/36/36/36
Piping
Main pipe
m
[ft]
5[16-3/8"]
Branch pipe 10 [32-3/4"]
Total pipe length 55 [180-1/8"]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz]
38.5 [85]
Outdoor
unit
Electric current A 39.5
Voltage V 230
Compressor frequency Hz 65 43
LEV open-
ing
Indoor unit
Pulse
230/230/230/275/275
BC controller (1/2/3) 2000/2000/260
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.66/0.91
[385/131]
2.65/0.91
[384/131]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.59/2.59
[375/375]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
85 [185] 76 [169]
Heat exchanger outlet
(TH3)
39 [102] 41 [106]
Accumulator inlet 8 [46] 14 [57]
Accumulator outlet 8 [46] 14 [57]
Compressor inlet 19 [66] 23 [73]
Compressor shell bottom 40 [104] 34 [93]
Indoor unit
LEV inlet 22 [72]
Heat exchanger inlet 9 [48]