[ VIII Test Run Mode ]
- 166 -
HWE0803A GB
Operation
Outdoor unit model
PURY-P120THMU-A
Model name of BC controller CMB-P104NU-G
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/-
[70°F/-]
Outdoor
8.3°C/6.1°C
[47°F/43°F]
Indoor unit
No. of connected units
Unit
4
No. of units in operation 4
Model - 30/30/30/30
Piping
Main pipe
m
[ft]
5[16-3/8"]
Branch pipe 10 [32-3/4"]
Total pipe length 45 [147-5/8"]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz]
22.5 [50]
Outdoor
unit
Electric current A 28.3
Voltage V 230
Compressor frequency Hz 81
LEV open-
ing
Indoor unit
Pulse
295/295/295/295
BC controller (1/2/3) 110/-/660
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.57/0.64
[372/92]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.54/2.22
[368/321]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
73 [163]
Heat exchanger outlet
(TH6)
2[36]
Accumulator inlet -1 [30]
Accumulator outlet -1 [30]
Compressor inlet -1 [30]
Compressor shell bottom 40 [104]
Indoor unit
LEV inlet 28 [82]
Heat exchanger inlet 67 [153]