Mitsubishi Electronics PURY-P144 Air Conditioner User Manual


 
[ IX Troubleshooting ]
- 291 -
HWE0803A GB
Check whether the BC board output signal corresponds with the solenoid valve operation correspond.
1) SVA, SVB, SVC
SVA, SVB, and SVC turn on or off according to the indoor unit operation mode.
SVM1 and SVM2
SVM1 and SVM2 turn on or off according to the indoor unit operation mode.
2) SVA, SVB, SVC
Measure the temperature at the upstream and downstream pipes and of SVA.
Measure the temperature at the upstream and downstream pipes and of SVA.
Mode
Cooling Heating Stopped Defrost Fan
Port
SVA ON OFF OFF OFF OFF
SVB OFF ON OFF OFF OFF
SVC ON OFF OFF OFF ON
Operation
mode
Cooling only Cooling main Heating only Heating main Defrost Stopped
SVM1 ON
Pressure dif-
ferential con-
trol OFF or
ON
OFF OFF ON OFF
SVM2 OFF OFF
Pressure dif-
ferential con-
trol OFF or
ON
Pressure dif-
ferential con-
trol OFF or
ON
OFF OFF