Mitsubishi Electronics PURY-P144 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 167 -
HWE0803A GB
2. 2-unit combination
(1) Cooling only operation
Operation
Outdoor unit model
PURY-P144TSHMU-A
PURY-P72THMU-A PURY-P72THMU-A
Model name of BC controller CMB-P108NU-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor 35°C/- [95°F/-]
Indoor unit
No. of connected units
Unit
4
No. of units in operation 4
Model - 36/36/36/36
Piping
Main pipe
m
[ft]
5[16-3/8"]
Branch pipe 10 [32-3/4"]
Total pipe length 45 [147-5/8"]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz]
34.1 [75]
Outdoor
unit
Electric current A 31.5
Voltage V 230
Compressor frequency Hz 43 43
LEV open-
ing
Indoor unit
Pulse
275/275/275/275
BC controller (1/2/3) 2000/2000/250
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.65/0.90
[384/130]
2.65/0.90
[384/130]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.59/2.59
[375/375]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
76 [169] 76 [169]
Heat exchanger outlet
(TH3)
41 [106] 41 [106]
Accumulator inlet 14 [57] 14 [57]
Accumulator outlet 14 [57] 14 [57]
Compressor inlet 23 [73] 23 [73]
Compressor shell bottom 34 [93] 34 [93]
Indoor unit
LEV inlet 24 [75]
Heat exchanger inlet 12 [54]