Mitsubishi Electronics PURY-P144 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 163 -
HWE0803A GB
[7] Standard Operation Data (Reference Data)
1. Single unit
(1) Cooling only operation
Operation
Outdoor unit model
PURY-P72THMU-A PURY-P96THMU-A
Model name of BC controller CMB-P104NU-G CMB-P104NU-G
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C
[80 °F/67 °F]
26.7°C/19.4°C
[80 °F/67 °F]
Outdoor
35°C/-
[95 °F/-]
35°C/-
[95°F/-]
Indoor unit
No. of connected units
Unit
32
No. of units in operation 3 2
Model - 24/24/24 48/48
Piping
Main pipe
m
[ft]
5 [16-3/8"] 5 [16-3/8"]
Branch pipe 10 [32-3/4"] 10 [32-3/4"]
Total pipe length 35 [114-13/16"] 25 [82]
Fan speed - Hi Hi
Amount of refrigerant
kg
[lbs-oz]
19.1 [42] 21.3 [47]
Outdoor
unit
Electric current A 15.4 23.2
Voltage V 230 230
Compressor frequency Hz 43 65
LEV open-
ing
Indoor unit
Pulse
180/200/220 387/387
BC controller (1/2/3) 2000/-/180 2000/-/170
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.65/0.90
[384/130]
2.66/0.93
[385/134]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.59/2.59
[375/375]
2.58/2.58
[374/374]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
76 [169] 85 [185]
Heat exchanger outlet
(TH3)
41 [106] 39 [102]
Accumulator inlet 14 [57] 8 [46]
Accumulator outlet 14 [57] 8 [46]
Compressor inlet 23 [73] 19 [66]
Compressor shell bottom 34 [93] 40 [104]
Indoor unit
LEV inlet 24[75] 19[66]
Heat exchanger inlet 12 [54] 6 [43]